Every ClearCalcs project has an optional button in the sidebar called 'Project Defaults'. These are a set of default/preset values for the country code in uestion.
They are carried through to every new calculation that is created. The purpose of this tutorial is to clarify the use of these defaults, and which calculators are impacted by each option.
Tip: You can still override any of these defaults in a specific calculator by selecting the field in question and manually typing over it. These defaults are purely to save you time, and you don't need to use them if you don't want to. If you copy a project, any project defaults will be copied along with the calculations.
The main sections in Project Defaults are:
1. Deflection Limits (EN 1990:2002 A1.4) 2. Building geometry (e.g. beam spacings, storey heights, roof slope) 3. Default Loads (e.g. default roof, floor, wall & window loads) 4. Load Combinations & Factors (e.g. Strength & Serviceability Combinations)
Some hard limits are provided in the Project Defaults which may override any deflection limit above. Of course you can always override these values in any of the calculators.
Deflection limits may be set once within Project Defaults, and then every calculator you create / have created will inherit these values. Of course you can always override these values in any of the calculators.
Timber columns are checked for the Instantaneous Deflection and Final Deflection (net). ClearCalcs does not support beam pre-camber.
Steel columns are typically checked for the Characteristic Deflection Limits only, however both the Frequent and Quasi-Permanent inputs are provided, if required by client and/or national annexes.
Do you want to set up default heights of each storey of your building? This can be used to create default column lengths every time you create a new calculation
Tip: You can find explanatory information & diagrams by expanding any label. For example, expanding "Floor Heights" above shows this:
Default spacings used to calculate distributed loads in rafters and joists. Refer to article What is tributary width? for details about how distributed loads are calculated.
Quick Tip: Did you know that rafters or joists may be linked into other beams (e.g. floor bearer) as a line load? This means you only have to create a single rafter / joist and then ClearCalcs will use the spacing to regularly space the reactions. Refer here for details. Of course the values may be overridden within each calculator. See example from the "Steel Beam" calculator:
Does your structure have space constraints? ClearCalcs will check the depth of your beam, and compare it with the Maximum Roof Beam Depth set below.
ClearCalcs performs a bearing check is completed for timber beams. The default bearing length can be set here, however may be overridden in each individual calculation.
Roof
Roof Default Load Table is dynamically set based on the selection of criteria for "Roof Permanent" and "Roof Imposed" Load selections.
Floors have default area loads depending on the structures' intended use.
The "Live Load Selection" is used to set the "Default Floor Loads" details in the dropdown menu.
Wall Default loads are used on Floor Lintel Calculators. These may be overridden within individual calculators.
ClearCalcs provides standard Load Combinations & Factors. These can be set to custom values. See below how to select these:
The value of the combination factors are defined in EN 1990:200 Table A1.1 - ψ factors for buildings. Eurocode snow location categories can be selected. For National Annexes that use custom snow categories, "Custom" snow factors need to be set instead:
A range of EN 1990:2002 load combinations are provided for Strength and Serviceability. These affect the load combinations in all design calculators (e.g. Timber & Steel Beam/Column).
Where EN1990:200 Eq 6.10a/b is used, a choice is given to consider Permanent Load only for equation 6.10(a), and a custom dead load reduction factor ξ may also be chosen:
Each calculation has "alternative" live load combinations, which are not intended to be applied at the same time (e.g. during construction imposed load vs post-construction residential loads). These are represented by QI, QI2 and QI3. When linking loads, you can choose to only transfer through the main load (i.e. the alternative construction load does not need to be applied to others part of the structure).
Generally this load shouldn’t actually be linked through the load path in the building - it should just be an alternate load for individual members only.
Select “Yes” here to exclude these loads from all load linking throughout this project.
Service load combinations are provided in EN 1990:2002 Eq (6.14) to (6.16) - characteristic, frequent and quasi-permanent. Each type of material (timber, steel, concrete) treats deflection limits slightly differently.
In EN1993 (steel), all 3 deflection combinations are used, although some codes may only require the use of the Characteristic Combination.
In EN1995 (timber), “Instantaneous” and “Final” deflection combinations are checked:
Defaults correspond to those recommended in EN 1990:2002, Tables A1.4
There are a variety of reasons why you may want to use Custom Combinations. ClearCalcs makes this easy to customise any of the inputs mentioned in Section 4(A) to 4(C) above. Here is a snapshot of how an input table looks. A note for combination factors is that a "-" means no factor or (1.0) is applied.
Tip: You can move Project Defaults between projects. Typically customers create a number of template projects that only have Project Defaults, which can be duplicated for each new project!
You have now customised your ClearCalcs project to make creating any calculations quick and easy!